Raypak Temp-Tracker Instruções de Operação Página 27

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
Vista de página 26
27
MODE 5
(With Default Settings Shown)
ADJUST MENU
(Page 1 of 3)
T
he Adjust menu items are the programmable settings
used to operate the system. Press and hold all three
b
uttons for one second to enter the Adjust menu, then
select the desired item using the Item button. Finally,
use the or button to make the adjustment (see
Fig. 6).
Item Field Range Description
Setting
1 to 8
MODE
Select the operating mode for the control.
PId or P
STAGE MODE
Select the staging operation to be either
automatic or manual.
(PId = automatic)
(P = proportional)
OFF,
70 to 220°F
(21 to 104°C)
BOILER TARGET
Select the boiler target temperature while
a setpoint demand is present.
35 to 85°F
(2 to 29°C)
OUTDOOR START
Select the outdoor starting temperature
used in the reset ratio for the heating
system. Typically set to the desired building
temperature.
-60 to 32°F
(-51 to 0°C)
OUTDOOR DESIGN
Select the outdoor design temperature used
in the reset ratio for the heating system. Set
to the coldest annual outdoor temperature
in the local area.
35 to 150°F
(2 to 66°C)
BOILER START
Select the starting water temperature used
in the reset ratio calculation for the heating
system. Typically set to the desired building
temperature.
70 to 230°F
(21 to 110°C)
BOILER DESIGN
Select the boiler design water temperature
used in the reset ratio calculation for the
heating system. Set to the boiler water
temperature required to heat the building on
the coldest annual outdoor temperature.
120 to 230°F
(49 to 110°C)
BOILER OUTLET MAXIMUM
Select the maximum boiler outlet
temperature. Exceeding this temperature
shuts o the burners.
Table M: Adjust Menu, Mode 5 (page 1 of 3)