MODE 3
(With Default Settings Shown)
ADJUST MENU
(Page 1 of 2)
T
he Adjust menu items are the programmable settings
used to operate the system. Press and hold all three
b
uttons for one second to enter the Adjust menu, then
select the desired item using the Item button. Finally,
use the or button to make the adjustment (see
Fig. 6).
Item Field Range Description
Setting
1 to 8
MODE
Select the operating mode for the control.
PId or P
STAGE MODE
Select the staging operation to be either
automatic or manual.
(PId = automatic)
(P = proportional)
OFF, 70 to
190°F
(21 to 88°C)
TANK TARGET
Select the dedicated domestic hot water
tank target temperature.
Au, 2 to 42°F
(1 to 23°C)
TANK DIFFERENTIAL
Select the dedicated domestic hot water tank
dierential. The DHW sensor temperature
must fall below this setting before the
burners will turn on.
120 to 225°F
(49 to 107°C)
BOILER OUTLET MAXIMUM
Select the maximum boiler outlet
temperature. Exceeding this temperature
shuts o the burners.
0:00 to 3:00 min
(1 second
increments)
FIRE DELAY
Select the amount of time required for
combustion pre-purging, ignition and the
ame to be established.
Note: This setting is only available when
STAGE MODE is set to Pld.
1 (Lo) or
2 (Med) or
3 (Hi)
BOILER MASS
Select the thermal mass of the boiler.
Note: This setting is only available when
STAGE MODE is set to PId.
Table J: Adjust Menu, Mode 3 (page 1 of 2)